• zopzao8이(가) 업데이트를 게시했습니다 4 년, 9 개월 전

    KDGH300-BG 50HZ
    Ratings
    Rated PowerkVA375
    kW300
    Voltage type50Hz, 380/220V, 3 phases and 4 wires
    *Ratings at 0.8 power factor
    Performance Data
    Engine Brand & ModelHGKT19
    Alternator Brand & ModelLSA47.2VS2/300KW
    Control SystemDeepsea DSE6120
    Standard Noise Level@7m (Soundproof Sets)75 dBA
    Circuit Breaker Type3 Poles MCCB
    Frequency & Phase50hz 3Phases + 4Wires
    Engine Speed (RPM)1500
    Fuel Consumption (Nm3/hr) 100% Load86.19
    * The above fuel consumption is calculate with the natural gas whose heat value is 35.8MJ/Nm3
    Dimensions and Weights
    ContentOpen typeSoundproof Sets
    Dimensions: (mm)L35005600
    W12502000
    H20202500
    Weights (kg)33804985
    Engine Brand & Model: HGKT19
    Engine Data
    No. of Cylinders6 in-lineEngine power(KW)341
    Cycle4 StrokeCylinder TypeWet
    Bore * Stroke (mm)159 * 159Compression Ratio11.5:1
    InductionTurbocharged & AftercooledDisplacement (L)18.9
    Cooling MethodWater cooledGoverning TypeElectronic
    Starting method24V DC motorCoolant capacity, including radiator (L)115
    Lubricant Oil15W40-CF4 or above gradeOil pan capacity (L)87
    Iginition system and sensor:
    ◇The generator uses ALTRONIC (ECU) and equipped the high voltage circuit to realize the high energy and best ignition of gas generator. The minimal speed of ignition is 100RMP and the maximal speed of ignition is 4000RMP, the ignition angle range from 5 to 35.
    ◇The core of ECU actually is computer chip, which has tre-buttons signal input ( rotated speed, load and temperature). According to the signal, the computer will act the right judge to do the positive cylinder, right time ignition and speed limited protection.
    ◇Check every circuit to see connecting joint whether is liable or damaged, high voltage winding whether damaged or leaking electricity.
    ◇Check the ignition of spank whether nomal, if not, please change it immediately, check the battery voltage not lower than 25V ( Because voltage too low will affect the normal running), please charge to the battery in time.
    Combining adjustment of shaft sensor and trigger vane:
    After installation of shaft sensor, it should adjust the location ot trigger vane. The method is to install the Cylinder one on the TDC( end point of compression) location, then justify of trigger vane small chip’s back limb front-end to the shaft sensor’s geometric center as following. Meanwhile, the depth of trigger vane’s inserting sensor is 9.5±0.2mm.
    If the gas intake pipe happed back flashing, please check:
    Whether ignition signal wire keep in the appointed position;
    Whether the inner gear of signal generator loosed;
    Whether ignition high voltage winding damage;
    Whether earth connecting liable.
    Problem Processing Method: Contact the manufacturer.
    If the power of generator is insufficient, please check:
    Whether the filter of voltage regulator valve clogged;
    Whether the air filter clogged;
    Whether the exhaust pipe clogged.
    Pressed air:
    Don’t use the pressed air or gas to clean clothes or body. The small drops can also cause serious damage in the situation of high pressure. China Gas Generator Set manufacturers
    website:http://www.camda-generator.com/gas-generator-set/